Chapter 4, Problem 35R

A 120-volt branch circuit supplies a resistive heating load of 10 amperes. The distance from the panel to the heater is approximately 140 ft. Calculate the voltage drop using (a) 14 AWG, (b) 12 AWG, (c) 10 AWG, (d) 8 AWG copper conductors. See 210.19(A), Informational Note No. 4 and 215.2(A)(1), Informational Note No. 2.

(a)

Expert Solution
Check Mark
To determine

Find the value of voltage drop in 14 AWG copper wire.

Answer to Problem 35R

The obtained value of voltage drop in 14 AWG copper wire is 8.79Volts drop_.

Explanation of Solution

Given data:

Supply voltage is 120-volt.

Current is 10 A.

The distance between panel and heater is approximately 140 ft.

14 AWG copper conductor.

Calculation:

Write the expression for voltage drop in single-phase circuit.

Ed=K×I×L×2CMA (1)

Here,

Ed is the voltage drop,

K is the approximate resistance in ohms per circular-mil foot at 75°C. The value of K for uncoated copper wire is 12.9 and for aluminum wire is 21.2.

I is the current, and

CMA is cross-sectional area of the conductors.

Modify Equation (1) for 14 AWG copper wire.

Ed(14AWG)=K×I×L×2CMA(14AWG) (2)

Refer TABLE 4-7 in the textbook for circular mil area (CMA) for many of the common conductors.

The value of CMA for 14 AWG is 4110.

Substitute 12.9 for K, 10 A for I, 140 ft for L, and 4110 for CMA(14AWG) in Equation (2) to find the voltage drop in 14 AWG copper wire.

Ed(14AWG)=12.9×10×140×24110=8.788Volts drop8.79Volts drop

Conclusion:

Thus, the obtained value of the voltage drop for 14 AWG copper wire is 8.79Volts drop_.

(b)

Expert Solution
Check Mark
To determine

Find the value of voltage drop in 12 AWG copper wire.

Answer to Problem 35R

The obtained value of the voltage drop for 12 AWG copper wire is 5.53Volts drop_.

Explanation of Solution

Given data:

12 AWG copper conductor.

Calculation:

Modify Equation (1) for 12 AWG copper wire.

Ed(12AWG)=K×I×L×2CMA(12AWG) (3)

Refer TABLE 4-7 in the textbook for circular mil area (CMA) for many of the common conductors.

The value of CMA for 12 AWG is 6530.

Substitute 12.9 for K, 10 A for I, 140 ft for L, and 6530 for CMA(12AWG) in Equation (3) to find the voltage drop in 12 AWG copper wire.

Ed(12AWG)=12.9×10×140×26530=5.531Volts drop5.53Volts drop

Conclusion:

Thus, the obtained value of voltage drop for 12 AWG copper wire is 5.53Volts drop_.

(c)

Expert Solution
Check Mark
To determine

Find the value of voltage drop in 10 AWG copper wire.

Answer to Problem 35R

The obtained value of voltage drop for 10 AWG copper wire is 3.48Volts drop_.

Explanation of Solution

Given data:

10 AWG copper conductor.

Calculation:

Modify Equation (1) for 10 AWG copper wire.

Ed(10AWG)=K×I×L×2CMA(10AWG) (4)

Refer TABLE 4-7 in the textbook for circular mil area (CMA) for many of the common conductors.

The value of CMA for 10 AWG is 10,380.

Substitute 12.9 for K, 10 A for I, 140 ft for L, and 10,380 for CMA(10AWG) in Equation (4) to find the voltage drop in 10 AWG copper wire.

Ed(10AWG)=12.9×10×140×210,380=3.479Volts drop3.48Volts drop

Conclusion:

Thus, the obtained value of voltage drop for 10 AWG copper wire is 3.48Volts drop_.

(d)

Expert Solution
Check Mark
To determine

Find the value of the voltage drop in 8 AWG copper wire.

Answer to Problem 35R

The obtained value of the voltage drop for 8 AWG copper wire is 2.19Volts drop_.

Explanation of Solution

Given data:

8 AWG copper conductor.

Calculation:

Modify Equation (1) for 8 AWG copper wire.

Ed(8AWG)=K×I×L×2CMA(8AWG) (5)

Refer TABLE 4-7 in the textbook for circular mil area (CMA) for many of the common conductors.

The value of CMA for 8 AWG is 16,510.

Substitute 12.9 for K, 10 A for I, 140 ft for L, and 16,510 for CMA(8AWG) in Equation (5) to find the voltage drop in 8 AWG copper wire.

Ed(8AWG)=12.9×10×140×216,510=2.187Volts drop2.19Volts drop

Conclusion:

Thus, the obtained value of the voltage drop for 8 AWG copper wire is 2.19Volts drop_.

Want to see more full solutions like this?

Subscribe now to access step-by-step solutions to millions of textbook problems written by subject matter experts!
Students have asked these similar questions
Most residential general lighting circuits are wired with 14-AWG copper conductors and are protected by 15-amp circuit breakers. However, there are many electricians who install 12-AWG copper conductors and protect them with 20-amp circuit breakers. How will you know which conductor size and which circuit breaker size will be used for the general lighting branch circuits in the house you are wiring?
1.The exciting current of an electromagnet is rated at 12 Amperes. When connected across a 122-Volt source, the current is 14 Amperes. Determine the ohms in a resistor which must be connected in series to limit the current to (a) rated value, and (b) 9 amperes.
Load in Figure 1 needs to be connected to Mains Switch Board (MSB) using multicore PVC cable. As a maintenance engineer, you need to proposed cable size for the load, Determine the following issues. 1) Calculate current demand for the circuit. 1) Detemine suitable MCCB (Model and nominal current rating) should be used to protect the load against over-current. im Propose suitable cable size for the load in Figure 1. iv) Calculate voltage drop of the proposed cable WITHOUT consider the cable reactance and voltage drop correction due to higher cable operating temperature v) Calculate voltage drop of the proposed cable BY consider the cable reactance and voltage drop correction due to higher cable operatıng temperature vi) If the multicore PVC eable is change into 3 single core PVC cables, what the suitable cable size. All other multicore cables not available. (25 + variable x) m (A) 30 m (B) (15 + variable b) m (C) Multicore PVC cable MCCB 95 kW. (400 + variable y) V. 0.85 p.f. Load MSB…

Chapter 4 Solutions

EBK ELECTRICAL WIRING RESIDENTIAL

Ch. 4 - For nonmetallic-sheathed cable, may the...Ch. 4 - Prob. 12RCh. 4 - Under what condition may nonmetallic-sheathed...Ch. 4 - a. What is the maximum distance permitted between...Ch. 4 - Prob. 15RCh. 4 - Prob. 16RCh. 4 - Prob. 17RCh. 4 - Prob. 18RCh. 4 - Prob. 19RCh. 4 - Circle the correct answer to the following...Ch. 4 - When running Type NM cable through a bored hole in...Ch. 4 - Where is the main service-entrance panel located...Ch. 4 - Is it permitted to use flexible metal conduit over...Ch. 4 - Liquidtight flexible metal conduit may serve as a...Ch. 4 - It is permissible for an electrician to connect...Ch. 4 - Terminals of switches and receptacles marked...Ch. 4 - Wire connectors marked AL/CU are suitable for use...Ch. 4 - A wire connector bearing no marking or reference...Ch. 4 - When Type NM cable is run through a floor, it must...Ch. 4 - When nonmetallic-sheathed cables are bunched or...Ch. 4 - In diagrams A and B, nonmetallic-sheathed cable is...Ch. 4 - The marking on the outer jacket of a...Ch. 4 - A 120-volt branch circuit supplies a resistive...Ch. 4 - In problem 35, it is desired to keep the voltage...Ch. 4 - Prob. 37RCh. 4 - The allowable ampacity of a 4 AWG THHN from Table...Ch. 4 - If, because of some obstruction in a wall space,...Ch. 4 - The recessed fluorescent luminaires installed in...Ch. 4 - Prob. 41RCh. 4 - What size overcurrent device protects the...Ch. 4 - May the 20-ampere small-appliance branch circuits...Ch. 4 - A 30-ampere branch circuit is installed for an...Ch. 4 - In many areas, metal framing members are being...Ch. 4 - Are set screwtype connectors permitted to be used...Ch. 4 - Most armored cable today has 90C conductors. What...Ch. 4 - If you saw two different types of SE cables, how...Ch. 4 - Circle the correct answer defining the type of...
Knowledge Booster
Background pattern image
Electrical Engineering
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
SEE MORE QUESTIONS
Recommended textbooks for you
Text book image
EBK ELECTRICAL WIRING RESIDENTIAL
Electrical Engineering
ISBN:9781337516549
Author:Simmons
Publisher:CENGAGE LEARNING - CONSIGNMENT
What is an electric furnace and how does it work?; Author: Fire & Ice Heating and Air Conditioning Inc;https://www.youtube.com/watch?v=wjAWecPGi0M;License: Standard Youtube License