A three-phase line with an impedance of
Load 1: Absorbs a total of 150 kW and 120 kvar.
Load 2: Delta connected with an impedance of
Load 3: 120 kVA at 0.6 PF leading.
If the line-to-neutral voltage at the load end of the line is 2000 v (rms), determine the magnitude of the line-to-line voltage at the source end of the line.
Trending nowThis is a popular solution!
Chapter 2 Solutions
Power System Analysis and Design (MindTap Course List)
- The instantaneous power absorbed by the load in a single-phase ac circuit, for a general R LC load under sinusoidal-steady-state excitation. is (a) Nonzero constant (b) Zero (c) Containing double-frequency componentsarrow_forwardTwo balanced Y-connected loads, one drawing 10 kW at 0.8 power factor lagging and the other IS kW at 0.9 power factor leading, are connected in parallel and supplied by a balanced three-phase Y-connected, 480-V source. (a) Determine the source current. (b) If the load neutrals are connected to the source neutral by a zero-ohm neutral wire through an ammeter, what will the ammeter read?arrow_forwardThree single-phase transformers, each rated 10MVA,66.4/12.5kV,60Hz, with an equivalent series reactance of 0.1 per unit divided equally between primary and secondary, are connected in a three-phase bank. The high-voltage windings are V-connected and their terminals are directly connected to a 115-kV three-phase bus. The secondary terminals are all shorted together. Find the currents entering the high-voltage terminals and leaving the low-voltage terminals if the low-voltage windings are (a) Y-connected and (b) - connected.arrow_forward
- Figure 3.32 shows the oneline diagram of a three-phase power system. By selecting a common base of 100 MVA and 22 kV on the generator side, draw an impedance diagram showing all impedances including the load impedance in per-unit. The data are given a follows: G:90MVA22kVx=0.18perunitT1:50MVA22/220kVx=0.10perunitT2:40MVA220/11kVx=0.06perunitT3:40MVA22/110kVx=0.064perunitT4:40MVA110/11kVx=0.08perunitM:66.5MVA10.45kVx=0.185perunit Lines I and 2 have series reactances of 48.4 and 65.43, respectively. At bus 4, the three-phase load absorbs 57 MVA at 10.45 kV and 0.6 power factor lagging.arrow_forwardThe Figure shows a balanced Y-A 3Ø circuit. The phase voltages of the Y-connected source are V, = 11020°, V, = 1102 - 120° and V. = 1102120°, Volts. The line impdedances are Z,=10+j5 Q each. The impedances of the A-connected load are ZA = 75+j255 N each. Determine: Line Currents, Phase Currents (load), Power drawn by the load. Ve ZA Vbarrow_forwardIn the circuit in the figure; L1 load draws 15 kVA with lagging power factor 0.6. The L2 load draws 6 kVA with a leading power factor of 0.8. According to this; What is the value of the complex power for the L2 load?arrow_forward
- The one-line diagram of a three-phase power system is shown in the above figure. The line impedances are in per- unit on a 100-MVA base, and the line admittances are neglected. ' qu V = 1.05200 0.01+ j0.025 300 + j200 MVA 3 0.015 + j0.035 150 MW 200 + j150 MVA 0.01 + j0.03 |V = 1.03 The admittance matrix (Y_bus)? The bus power in per-unit?arrow_forwardDraw Wye- Delta three phase transformers connection ( no-load and full-load) in Lt-spicearrow_forwardVA-120 V4120 Z₁ volt In lc c ZA Three-phase source Feeder lines Balanced load In the above circuit diagram, we have source impedance Zg = 0.05+j0.15 ohm, Z₁ = 0.1+j0.2 ohm and per phase impedance in the balanced Delta connected load, Z₁ = 12+j9 ohm. RMS value of source voltage is 200 volt. Phase sequence is as shown in the diagram. RMS value of current Ic= ampere Phase angle of le= degree RMS value of line voltage VCA = B JAB Inc ICAarrow_forward
- A Y-connected balanced three-phase source is connected to a three-phase balanced load through a four-wire three-phase cable. The generator has an impedance of 0.1+j0.3 Q/phase. Each phase of the cable has an impedance of 2+2j 2 The phase "B" load voltage is 102-140° kV. The impedance of each phase of the Y-connected load is 3-j5 Q/phase. For a negative sequence: 1- tto pointe) Calculate "terminal" phase voltage of phases "a" and "c" of generator. 2- E points] Calculate Vab and Vca across the load. 5 points Calculate three phase power supplied by the source. 4- 10 point] Calculate three phase power losses.arrow_forwardThe plant capacity of a 3-phase generating station consists of two 8 MVA generators of reactance 14·5%each and one 4 MVA generator of reactance 9·5%. These are connected to a common bus-bar fromwhich loads are taken through a number of 3 MVA step-up transformers each having 4% reactance.Determine the MVA rating of the circuit breakers on (i) L.V. side and (ii) H.V. side. Reactances givenare based on the MVA of each equipment. [(i) 15·24 MVA (ii) 50·25 MVA]arrow_forwardA three-phase system has balanced conditions so that the per-phase circuit representation can be used as shown in Figure 1 Select the turns ratio of the step-up and step-down transformers that the system operates with an efficiency greater than 99 percent. Moreover, find the complex power (received or given) of all components in the circuit and the V1 and V2 voltages. The load voltage is specified as 4 kV rms, and the load impedance is 4/3 ohm. ..arrow_forward