A uniform 2-wire d.c. distributor 500 meters long is loaded with 0.4 ampere/ meter and is fed at one end. If the maximum permissible voltage drop is not to exceed 10 V, find the cross-sectional area of the distributor conductor. Taker 1-7 X 10- cm. %3D

EBK ELECTRICAL WIRING RESIDENTIAL
19th Edition
ISBN:9781337516549
Author:Simmons
Publisher:Simmons
Chapter19: Special-purpose Outlets-water Pump, Water Heater
Section19.2: Water Heater Branch Circuit
Problem 1R
icon
Related questions
Question
honor 8X
A uniform 2-wire d.c. distributor 500 meters long is loaded with 0.4
ampere/ meter and is fed at one end. If the maximum permissible
voltage drop is not to exceed 10 V, find the cross-sectional area of the
distributor conductor. Taker= 1-7 X 10- cm.
,50.4 Am
max Voltuge Sop)
= lov
Transcribed Image Text:honor 8X A uniform 2-wire d.c. distributor 500 meters long is loaded with 0.4 ampere/ meter and is fed at one end. If the maximum permissible voltage drop is not to exceed 10 V, find the cross-sectional area of the distributor conductor. Taker= 1-7 X 10- cm. ,50.4 Am max Voltuge Sop) = lov
Expert Solution
steps

Step by step

Solved in 3 steps with 2 images

Blurred answer
Knowledge Booster
Dielectric breakdown
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
EBK ELECTRICAL WIRING RESIDENTIAL
EBK ELECTRICAL WIRING RESIDENTIAL
Electrical Engineering
ISBN:
9781337516549
Author:
Simmons
Publisher:
CENGAGE LEARNING - CONSIGNMENT
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning
Electric Motor Control
Electric Motor Control
Electrical Engineering
ISBN:
9781133702818
Author:
Herman
Publisher:
CENGAGE L