The three phase power and line-line ratings of the below electric power system is given below: V. Vm G G: 50 MVA 22 KV X= 4% T: 50 MVA 22/40 KV X= 496 M: 43.2 MVA 36 KV X= 4% By choosing 100 MVA and 22 KV on the generator side as base values. the new per unit impedance of the generator is and the new perunit impedance of the motor is None of these 8.333% Impedan 11.43% 7,5% 10.238% erunit on a100MVA. 100 KV base. The load at bus 2 1s S2= 16MW - 32 MVAR, and the load at bus 3 is 5OMVA at 0.8 pf lagging. it is required to hold the voltage a

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.36P: Three single-phase two-winding transformers, each rated 25MVA,34.5/13.8kV, are connected to form a...
icon
Related questions
icon
Concept explainers
Question
The three phase power and line-line ratings of the below electric power system is given below:
V.
Vm
G
G: 50 MVA
22 KV
X= 4%
T: 50 MVA
22/40 KV
X= 4%
M: 43.2 MVA
36 KV
X= 4%
By choosing 100 MVA and 22 KV on the generator side as base values, the new per unit impedance of the generator is
and the new perunit impedance of the
motor is
None of these
8.333%
Impedan 11.43%
7.5%
10.238%
erunit on a100MVA. 100 KV base. The load at bus 2 s S2= 16MW - 32 MVAR, and the load at bus 3 is 5OMVA at 0.8 pf lagging. It is required to hold the
voltage a
Transcribed Image Text:The three phase power and line-line ratings of the below electric power system is given below: V. Vm G G: 50 MVA 22 KV X= 4% T: 50 MVA 22/40 KV X= 4% M: 43.2 MVA 36 KV X= 4% By choosing 100 MVA and 22 KV on the generator side as base values, the new per unit impedance of the generator is and the new perunit impedance of the motor is None of these 8.333% Impedan 11.43% 7.5% 10.238% erunit on a100MVA. 100 KV base. The load at bus 2 s S2= 16MW - 32 MVAR, and the load at bus 3 is 5OMVA at 0.8 pf lagging. It is required to hold the voltage a
The three phase power and line-line ratings of the below electric power system is given below:
T
Vm
6.
M
G: 50 MVA
22 KV
X= 4%
T: 50 MVA
22/40 KV
X= 4%
M: 43.2 MVA
36 KV
X= 4%
By choosing 100 MVA and 22 KV on the generator side as base values. the new per unit impedance of the generator is
and the new perunit impedance of the
motor is
49%
8%
None of these
16%
Impedances are marked in perunit on a 100MVA. 100 KV base. The load at bus 2 is S2= 16MW - J32 MVAR. and the load at bus 3 15 5OMIVA at 0,8 pf lagging. It is required to hold the
Transcribed Image Text:The three phase power and line-line ratings of the below electric power system is given below: T Vm 6. M G: 50 MVA 22 KV X= 4% T: 50 MVA 22/40 KV X= 4% M: 43.2 MVA 36 KV X= 4% By choosing 100 MVA and 22 KV on the generator side as base values. the new per unit impedance of the generator is and the new perunit impedance of the motor is 49% 8% None of these 16% Impedances are marked in perunit on a 100MVA. 100 KV base. The load at bus 2 is S2= 16MW - J32 MVAR. and the load at bus 3 15 5OMIVA at 0,8 pf lagging. It is required to hold the
Expert Solution
steps

Step by step

Solved in 2 steps with 1 images

Blurred answer
Knowledge Booster
Load flow analysis
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning