Open-circuit test Short-circuit test Voc = 480 V Vsc = 10.0 V loc = 0.41 A Isc = 10.6 A %3D Poc = 38 W Psc = 26 W A single-phase 10-kVA, 480/1120 -V transformer is to be used as an auto transformer tying a 600V distribution line to a 480-V load. When it is tested as a conventional transformer, the following values are measured on the primary (480-V) side of the transformer: a. Find the per-unit equivalent circuit of this transformer when it is connected in the conventional manner. b. What is the efficiency of the transformer at rated conditions and unity power factor? c. What is the voltage regulation at those conditions? d. Sketch the transformer connections when it is used as a 600/480-V step-down autotransformer.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.34P: Three single-phase, two-winding transformers, each rated 450MVA,20kV/288.7kV, with leakage reactance...
icon
Related questions
icon
Concept explainers
Question
Open-circuit test
Short-circuit test
Voc = 480 V
Vsc = 10.0 V
loc = 0.41 A
Isc = 10.6 A
%3D
Poc = 38 W
Psc = 26 W
A single-phase 10-kVA, 480/1120 -V transformer is to be used as an auto transformer
tying a
600V distribution line to a 480-V load. When it is tested as a conventional
transformer, the
following values are measured on the primary (480-V) side of the transformer:
a. Find the per-unit equivalent circuit of this transformer when it is connected in the
conventional manner.
b. What is the efficiency of the transformer at rated conditions and unity power
factor?
c. What is the voltage regulation at those conditions?
d. Sketch the transformer connections when it is used as a 600/480-V step-down
autotransformer.
Transcribed Image Text:Open-circuit test Short-circuit test Voc = 480 V Vsc = 10.0 V loc = 0.41 A Isc = 10.6 A %3D Poc = 38 W Psc = 26 W A single-phase 10-kVA, 480/1120 -V transformer is to be used as an auto transformer tying a 600V distribution line to a 480-V load. When it is tested as a conventional transformer, the following values are measured on the primary (480-V) side of the transformer: a. Find the per-unit equivalent circuit of this transformer when it is connected in the conventional manner. b. What is the efficiency of the transformer at rated conditions and unity power factor? c. What is the voltage regulation at those conditions? d. Sketch the transformer connections when it is used as a 600/480-V step-down autotransformer.
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 10 steps with 13 images

Blurred answer
Knowledge Booster
Load flow analysis
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning