Figure 7.4 shows two 11 kV generators feeding a 132 kV double circuit line through gen- erator transformers. Each 132 kV line is 40 km long and with an inductive reactance of 0.40/km. Calculate the fault level for a three-phase fault at: Gen.1 11 kV 125 MVA X = 28% 11/132 kV 125 MVA X = 18% 40km B a. Point A on the busbar close to generator 1. b. Point B at the mid-point of one of the lines. A Gen.2 11 kV 75 MVA X = 18% 132/11 KV 90 MVA X = 12% Use a 100 MVA base for the calculation, express your answer in Amperes and ignore the effect of any system loads.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter7: Symmetrical Faults
Section: Chapter Questions
Problem 7.14P: Equipment ratings for the five-bus power system shown in Figure 7.15 are as follows: Generator G1:Â...
icon
Related questions
icon
Concept explainers
Question
I need the answer as soon as possible
Figure 7.4 shows two 11 kV generators feeding a 132 kV double circuit line through gen-
erator transformers. Each 132 kV line is 40 km long and with an inductive reactance of
0.42/km. Calculate the fault level for a three-phase fault at:
Gen.1
11 kV
125 MVA
X = 28%
11/132 kV
125 MVA
X = 18%
40km
B
a. Point A on the busbar close to generator 1.
b. Point B at the mid-point of one of the lines.
A
Gen.2
11 kV
75 MVA
X = 18%
132/11 kV
90 MVA
X = 12%
Use a 100 MVA base for the calculation, express your answer in Amperes and ignore
the effect of any system loads.
Transcribed Image Text:Figure 7.4 shows two 11 kV generators feeding a 132 kV double circuit line through gen- erator transformers. Each 132 kV line is 40 km long and with an inductive reactance of 0.42/km. Calculate the fault level for a three-phase fault at: Gen.1 11 kV 125 MVA X = 28% 11/132 kV 125 MVA X = 18% 40km B a. Point A on the busbar close to generator 1. b. Point B at the mid-point of one of the lines. A Gen.2 11 kV 75 MVA X = 18% 132/11 kV 90 MVA X = 12% Use a 100 MVA base for the calculation, express your answer in Amperes and ignore the effect of any system loads.
Expert Solution
steps

Step by step

Solved in 5 steps with 4 images

Blurred answer
Knowledge Booster
Fault analysis
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning