A commercial refrigerator with refrigerant-134a as the working fluid is used to keep the refrigerated space at -30°C by rejecting its waste heat to cooling water that enters the condenser at 18°C at a rate of 0.29 kg/s and leaves at 26°C. The refrigerant enters the condenser at 1.2 MPa and 65°C and leaves at 42°C. The inlet state of the compressor is 60 kPa and -34°C and the compressor is estimated to gain a net heat of 430 W from the surroundings. The heat exchanger loses no heat to the environment.

Refrigeration and Air Conditioning Technology (MindTap Course List)
8th Edition
ISBN:9781305578296
Author:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Chapter44: Geothermal Heat Pumps
Section: Chapter Questions
Problem 13RQ: If 14 gpm of water is flowing through an open-loop heat pump with a temperature difference of 7F,...
icon
Related questions
Question
!
Required information
NOTE: This is a multi-part question. Once an answer is submitted, you will be unable to return to this part.
A commercial refrigerator with refrigerant-134a as the working fluid is used to keep the refrigerated space at -30°C by
rejecting its waste heat to cooling water that enters the condenser at 18°C at a rate of 0.29 kg/s and leaves at 26°C. The
refrigerant enters the condenser at 1.2 MPa and 65°C and leaves at 42°C. The inlet state of the compressor is 60 kPa and
-34°C and the compressor is estimated to gain a net heat of 430 W from the surroundings. The heat exchanger loses no
heat to the environment.
26°C ↑
42°C
Condenser
Expansion
valve
Evaporator
OL
Water
18°C
2
kW.
1.2 MPa
65°C
W;
in
Compressor
60 kPa
-34°C
Determine the refrigeration load. (Take the required values from saturated refrigerant-134a tables and steam tables.)
(You must provide an answer before moving on to the next part.)
The refrigeration load is
Transcribed Image Text:! Required information NOTE: This is a multi-part question. Once an answer is submitted, you will be unable to return to this part. A commercial refrigerator with refrigerant-134a as the working fluid is used to keep the refrigerated space at -30°C by rejecting its waste heat to cooling water that enters the condenser at 18°C at a rate of 0.29 kg/s and leaves at 26°C. The refrigerant enters the condenser at 1.2 MPa and 65°C and leaves at 42°C. The inlet state of the compressor is 60 kPa and -34°C and the compressor is estimated to gain a net heat of 430 W from the surroundings. The heat exchanger loses no heat to the environment. 26°C ↑ 42°C Condenser Expansion valve Evaporator OL Water 18°C 2 kW. 1.2 MPa 65°C W; in Compressor 60 kPa -34°C Determine the refrigeration load. (Take the required values from saturated refrigerant-134a tables and steam tables.) (You must provide an answer before moving on to the next part.) The refrigeration load is
Expert Solution
steps

Step by step

Solved in 2 steps with 1 images

Blurred answer
Knowledge Booster
Refrigeration and Air Conditioning
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, mechanical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Refrigeration and Air Conditioning Technology (Mi…
Refrigeration and Air Conditioning Technology (Mi…
Mechanical Engineering
ISBN:
9781305578296
Author:
John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:
Cengage Learning