2. THE EVENTS OF A CASCADE, A PLIT-STAGE, LOW-TEMPERATURE REFRIGERATING CYCLE ARE AS FOLLOWS: AN AMMONIA VAPOR COMPRESSION SYSTEM OPERATES BETWEEN - 10C AND 33C WITH SATURATED LIQUID ON THE HIGH SIDE OF THE EXPANSION VALVE AND SATURATED VAPOR ENTERING THE COMPRESOR WHOSE VOLUMETRIC EFFICIENCY iS 89%. A R-11 COMPRESSION SYSTEM OPERATES BETWEEN -25C AND OC WITH SATURATED LIQUID ENTERING THE EXPANSION VALVE AND SATURATED VAPOR ENTERING THE COMPRESSOR WHOSE VOLUMETRIC EFFICIENCY IS 85%. THE AMMONIA EVAPORATOR SERVES AS THE CONDENSER OF THE R-11. FOR THE IDEAL CYCLE AND 10KW OF REFRIGERATION, FIND (a) THE DISPLACEMENT RATE OF EACH COMPRESSOR, AND (b) THE TOTAL ACTUAL POWER REQUIRED FOR COMPRESSION EFFICIENCIES OF 85%.

Refrigeration and Air Conditioning Technology (MindTap Course List)
8th Edition
ISBN:9781305578296
Author:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Chapter28: Special Refrigeration Applications
Section: Chapter Questions
Problem 15RQ: Why is two-stage compression popular for extra-low-temperature refrigeration systems?
icon
Related questions
Question
2. THE EVENTS OF A CASCADE, A PLIT-STAGE, LOW-TEMPERATURE REFRIGERATING CYCLE ARE
AS FOLLOWS: AN AMMONIA VAPOR COMPRESSION SYSTEM OPERATES BETWEEN - 10C AND
33C WITH SATURATED LIQUID ON THE HIGH SIDE OF THE EXPANSION VALVE AND SATURATED
VAPOR ENTERING THE COMPRESOR WHOSE VOLUMETRIC EFFICIENCY IS 89%. A R-11
COMPRESSION SYSTEM OPERATES BETWEEN -25C AND OC WITH SATURATED LIQUID
ENTERING THE EXPANSION VALVE AND SATURATED VAPOR ENTERING THE COMPRESSOR
WHOSE VOLUMETRIC EFFICIENCY IS 85%. THE AMMONIA EVAPORATOR SERVES AS THE
CONDENSER OF THE R-11. FOR THE IDEAL CYCLE AND 10KW OF REFRIGERATION, FIND (a) THE
DISPLACEMENT RATE OF EACH COMPRESSOR, AND (b) THE TOTAL ACTUAL POWER REQUIRED
FOR COMPRESSION EFFICIENCIES OF 85%.
Transcribed Image Text:2. THE EVENTS OF A CASCADE, A PLIT-STAGE, LOW-TEMPERATURE REFRIGERATING CYCLE ARE AS FOLLOWS: AN AMMONIA VAPOR COMPRESSION SYSTEM OPERATES BETWEEN - 10C AND 33C WITH SATURATED LIQUID ON THE HIGH SIDE OF THE EXPANSION VALVE AND SATURATED VAPOR ENTERING THE COMPRESOR WHOSE VOLUMETRIC EFFICIENCY IS 89%. A R-11 COMPRESSION SYSTEM OPERATES BETWEEN -25C AND OC WITH SATURATED LIQUID ENTERING THE EXPANSION VALVE AND SATURATED VAPOR ENTERING THE COMPRESSOR WHOSE VOLUMETRIC EFFICIENCY IS 85%. THE AMMONIA EVAPORATOR SERVES AS THE CONDENSER OF THE R-11. FOR THE IDEAL CYCLE AND 10KW OF REFRIGERATION, FIND (a) THE DISPLACEMENT RATE OF EACH COMPRESSOR, AND (b) THE TOTAL ACTUAL POWER REQUIRED FOR COMPRESSION EFFICIENCIES OF 85%.
Expert Solution
steps

Step by step

Solved in 5 steps with 1 images

Blurred answer
Knowledge Booster
Refrigeration and Air Conditioning
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, mechanical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Refrigeration and Air Conditioning Technology (Mi…
Refrigeration and Air Conditioning Technology (Mi…
Mechanical Engineering
ISBN:
9781305578296
Author:
John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:
Cengage Learning